Product overview
PTC-DP/GP is used to measure the liquid level of the medium with working pressure
To prevent the medium in the pipe from directly entering the pressure sensor assembly in the converter, the connection between double flange liquid level transmitter pressure measurement flange and converter is realized by the capillary tube fill with silicone oil and other substances;
The double flange liquid level transmitter applies to measurement of liquid level of clean liquid medium and the medium which is easily crystallized, contains solid impurities and is viscous.
Product application
Due to height difference when two flanges are installed, the transfer should be added at the moment of adjustment. The negative transfer is added to the negative pressure remote transmission flange above. The computing method is as follows:
Measuring range: P=r Negative transfer: B=r0h-rH0 r- specific gravity of the measured medium r0-specific gravity of silicone oil 0.97g/cm3 in the formula
For example: It's known that H=800mm, H0=250mm, h=1300mm, r=1.2g/cm3
Measuring range: P=r·H=1.2×800=960mmH2O
Negative transfer: B=r0h-rH0=0.97×1300-1.2×250=961≈960mmH20
Before installation, the measuring range should be adjusted to -960~0mmH20
Measurement of liquid interface
Stress on the positive pressure side: PH=r1(H0+H1+H-H2)+r2(H2+h0) Stress on the negative pressure side: PL= r1H0+r0(H1+H+h0)
Differential pressure: △P=P H-P L=r1(H1+H)+r2h0-r(H1+H+h0)+(r2-r2)H2
Transfer: B=r1(H1+H)+r2h0-r0(H1+H+h0) Measuring range: P=(r2-r2)H
r0-specific gravity of silicone oil H-maximum interface height.
Product model selection
PTC-LD | Remote transmission differential pressure transmitter | |||||
PTC-LG | Remote transmission pressure transmitter | |||||
Code | Measuring range KPa | |||||
3 | 0-1.3~7.5 | |||||
4 | 0-6.2~37.4 | |||||
5 | 0-31.1~186.8 | |||||
6 | 0-117~690 | |||||
7 | 0-345~2068 | |||||
Code | Output | |||||
E | 4-20mADC | |||||
S | Intelligent type | |||||
Code | Flange material | |||||
22 | 316SST | |||||
Code | Additional functions | |||||
S1 | One remote transmission device | |||||
S2 | Two remote transmission devices | |||||
Code | Option | |||||
M1 | 0-100% linear dial indicator | |||||
M2 | LED display meter | |||||
M3 | LCD display meter | |||||
B1 | Pipe mounting bend bracket | |||||
B2 | Plate mounting bend bracket | |||||
B3 | Pipe mounting flat bracket | |||||
d | Flame-proof type dⅡBT4 | |||||
i | Intrinsic safety type iaⅡCT6 |